SURFACE PIPING SINGLE SOFTENER SYSTEMS WITH FRP TANK
Dissolved calcium magnesium ions in water cause hardness in water. Aqualine water softening systems; These are systems that remove Calcium (Ca) and Magnesium (Mg) ions in water that cause hardness. For this reason, the softening system provides the removal of the hardness in the water and the softening of the drinking water, as well as the improvement of the taste of the water.
Softening systems automatically perform regeneration processes on the desired day of the week, at the desired time, without any intervention. The resin that reaches saturation regenerates with salt water and is cleaned from calcium and magnesium ions.
TECHNICIAL FEATURES WCY brand with FRP tank Aqualine brand cationic resin Maximum working pressure 6 bar Pneumatic actuated butterfly valves (Optional Electric Actuator option) Sub-collection structure lateral diffuser PVC-U material surface piping (on epoxy painted skid) Sample taps and manometers at system inputs and outputs PLC based Siemens logo control panel (Optional touch screen option) Electricity 220V / 50 Hz / 1 pH Consumption of 150 grams of salt is accepted for 1 liter of resin. Resin capacity 6000 Fr / liter resin is accepted. Dry instrument air supply required for the operation of pneumatic valves belongs to the customer. Recommended compressor capacity is minimum 100 Lt / min @ 8 bar